< Back

Overview

The 24 - 220 kVA range provides reliable power for today's world with a competitive offering that delivers everything you need. Providing unrivalled quality, the 24 - 220 kVA range of products offers a trusted performance with an enhanced choice of options, optimising the range for a variety of diverse applications and environments. Designed with the demands of today's world in mind, this range will deliver power solutions in all sectors, from industry and retail to finance and healthcare.

Generator Set Specifications

Minimum Rating 82.0 kVA / 82.0 kW 82.0 kVA / 82.0 kW Less
Maximum Rating 90.0 kVA / 90.0 kW 90.0 kVA / 90.0 kW Less
Voltage 220-240 Volts 220-240 Volts Less
Frequency 50 hz 50 hz Less
Speed 1500 RPM 1500 RPM Less
50 Hz Prime 82.0 kVA / 82.0 kW 82.0 kVA / 82.0 kW Less
50 Hz Standby 90.0 kVA / 90.0 kW 90.0 kVA / 90.0 kW Less
60 Hz Prime Less
60 Hz Standby Less

Generator Set Configurations

Emissions/Fuel Strategy EU Stage IIIA emissions compliant. EU Stage IIIA emissions compliant. Less

Engine Specifications

Engine Model Perkins® 1104D-E44TAG2 Perkins® 1104D-E44TAG2 Less
Compression Ratio 16.2:1 16.2:1 Less
Governor Type Electronic Electronic Less
Bore 105 mm (4.1 in) 105 mm (4.1 in) Less
Stroke 127 mm (5 in) 127 mm (5 in) Less
Displacement 4.4l (268.5 cu. in) 4.4l (268.5 cu. in) Less

FG Wilson Diesel Engine

Perkins Engine

Alternator

Benefiting from a choice of leading alternators, the range incorporates the Marelli alternator as standard across three phase models.

PowerWizard 1.1

The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

P90-6S Standard Equipment

Engine
  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown

Cooling
  • Radiator & Cooling Fan
  • Coolant Drain Valve
  • Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix

Exhaust
  • Exhaust flange outlet
  • Exhaust stub pipe and gasket

Fuel
  • 8 Hr Fuel Tank
  • Fuel Fittings for Local and Remote Feed

Alternator
  • Leroy Somer
  • SHUNT Excitation
  • IP23 Protection

Control Panel
  • PowerWizard 1.1

Mounting
  • Base, Formed Steel with Single wall Fuel Tank
  • Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
  • Anti-vibration mounts
  • Battery Tray and Cables

P90-6S Optional Equipment

Exhaust
  • Industrial, Residential, Critical Silencers

Alternator
  • Quadrature Droop Kit (AR6)
  • Anti-Condensation Heater and Panel Circuitry (AH1)

Control Panels
  • PowerWizard 1.1+ Control Panel (PWT1.1+)
  • PowerWizard 2.1 Control Panel (PWT2.1)

Starting/Charging
  • Lead Acid battery (Dry)

General
  • Upgrade to Standard Set for "CE" Certification
  • EEC Declaration of Conformity
  • Narrow, Wide or Skid Base
  • Sound attenuated, steel or galvanised enclosure
  • Defra bunded fuel tanks (FB4)