< Back

Overview

225 to 375 kVA Diesel Generator Sets. As your power needs increase, this cost effective generator set range delivers a powerful performance with world class power density. Compact and durable, they can easily be manoeuvred into position, whatever the installation conditions.

Generator Set Specifications

Minimum Rating 312.5 kVA / 250.0 kW 312.5 kVA / 250.0 kW Less
Maximum Rating 343.8 kVA / 275.0 kW 343.8 kVA / 275.0 kW Less
Voltage 127-480 Volts 127-480 Volts Less
Frequency 60 Hz 60 Hz Less
Speed 1800 RPM 1800 RPM Less
50 Hz Prime - / - - / - Less
50 Hz Standby - / - - / - Less
60 Hz Prime 312.5 kVA / 250.0 kW 312.5 kVA / 250.0 kW Less
60 Hz Standby 343.8 kVA / 275.0 kW 343.8 kVA / 275.0 kW Less

Generator Set Configurations

Emissions/Fuel Strategy Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Less

Engine Specifications

Engine Model Perkins® 1506A-E88TAG4 Perkins® 1506A-E88TAG4 Less
Bore 112.0 mm (4.4 in) 112.0 mm (4.4 in) Less
Displacement 8.8l (537.0 cu. in) 8.8l (537.0 cu. in) Less
Stroke 149.0 mm (5.9 in) 149.0 mm (5.9 in) Less
Compression Ratio 16.1:1 16.1:1 Less
Governor Type Electronic Electronic Less

FG Wilson Diesel Engine

Perkins Engine

Alternator

Combined with the Leroy Somer alternator, providing Ingress Protection IP23 as standard, a trusted performance is guaranteed..

Power Wizard 1.1 +

The FG Wilson PowerWizard range of digital control panels, combine straightforward menu navigation with advanced metering and protection technology. They are used in automatic mains failure applications in conjunction with transfer panels. Our PowerWizard range allows you to monitor and control your generator set with ease, whilst ensuring your unit operates within safe parameters and provides important diagnostic information when needed.

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

P344-3 Standard Equipment

Engine
  • Air Cleaner
  • Lube oil drain valve
  • Engine filled with lubrication oil
  • High Coolant Temperature Shutdown
  • Low Oil Pressure Shutdown

Cooling
  • Coolant Drain Valve
  • Fan, Fan drive and battery charging Alternator drive fully guarded to meet EC Machinery Directive
  • Cooling System filled with Coolant mix
  • Radiator and Cooling Fan

Exhaust
  • Exhaust stub pipe and gasket

Fuel
  • 8 Hr Fuel Tank
  • Fuel Fittings for Local and Remote Feed

Alternator
  • Leroy Somer
  • SHUNT Excitation
  • IP23 Protection
  • Coastal Insulation Protection

Control Panel
  • PowerWizard 1.1+

Mounting
  • Base, Formed Steel with Single wall Fuel Tank
  • Certified Base Mounted Lifting Eyes, and Rear Drag Eyelets
  • Battery Tray and Cables

P344-3 Optional Equipment

Exhaust
  • Industrial, Residential, Critical Silencers

Alternator
  • Quadrature Droop Kit (AR6)
  • Anti-Condensation Heater and Panel Circuitry (AH1)

Control Panels
  • PowerWizard 2.1 Control Panel (PWT2.1)
  • EasYgen 2500 control panel

Starting/Charging
  • Calcium battery (Dry)

General
  • Upgrade to Standard Set for "CE" Certification
  • Compact Skid Base for Open Sets
  • Sound attenuated, steel or galvanised enclosure
  • Dual wall fuel tanks