The 24 - 220 kVA range provides reliable power for today's world with a competitive offering that delivers everything you need. Providing unrivalled quality, the 24 - 220 kVA range of products offers a trusted performance with an enhanced choice of options, optimising the range for a variety of diverse applications and environments. Designed with the demands of today's world in mind, this range will deliver power solutions in all sectors, from industry and retail to finance and healthcare.

Generator Set Specifications

Minimum Rating 45 kVA / 36 kW 45 kVA / 36 kW Less
Maximum Rating 56.3 kVA / 45.0 kW 56.3 kVA / 45.0 kW Less
Voltage 120-380 Volts 120-380 Volts Less
Frequency 50 Hz or 60 Hz 50 Hz or 60 Hz Less
Speed 1500 or 1800 RPM 1500 or 1800 RPM Less
50 Hz Prime 45 kVA / 36 kW 45 kVA / 36 kW Less
50 Hz Standby 49.2 kVA / 39.4 kW 49.2 kVA / 39.4 kW Less
60 Hz Prime 50.0 kVA / 40.0 kW 50.0 kVA / 40.0 kW Less
60 Hz Standby 56.3 kVA / 45.0 kW 56.3 kVA / 45.0 kW Less

Generator Set Configurations

Emissions/Fuel Strategy Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Less

Engine Specifications

Engine Model Perkins® 1103A-33TG1 Perkins® 1103A-33TG1 Less
Compression Ratio 17.25:1 17.25:1 Less
Governor Type Mechanical Mechanical Less
Bore 105 mm (4.1 in) 105 mm (4.1 in) Less
Stroke 127 mm (5 in) 127 mm (5 in) Less
Displacement 3.3l (201.4 cu. in) 3.3l (201.4 cu. in) Less

FG Wilson Diesel Engine

Perkins Engine

Alternator

Benefiting from a choice of leading alternators, the range incorporates the WEG alternator as standard across three phase models.

PowerWizard 1.1

The FG Wilson PowerWizard range allows you to monitor and control your generator set with ease, providing important diagnostic information whilst ensuring your unit operates within safe parameters.

Design Criteria

Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support

FG Wilson manufactures product in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.

P56-1 Standard Equipment

Engine
  • 3-POLE circuit breaker
  • Fully adjustable electronic governor
  • Lube oil drain valve

Cooling
  • 50% antifreeze (Protection to -36˚C)
  • Engine-mounted fuel/water separator
  • Coolant drain valve

Fuel
  • 8 Hr Fuel Tank

Alternator
  • WEG
  • Engine-mounted battery charging alternator
  • IP21 Protection for alternator

Control Panel
  • PowerWizard 1.1

Mounting
  • Robust steel constructed base frame
  • Battery connection cables, tray and clamp

P56-1 Optional Equipment

Exhaust
  • Industrial, Residential, Critical Silencers
  • Industrial silencer (10 dB)
  • Residential silencer (25 dB)
  • Critical silencer (35 dB)
  • Silencer installation kit

Control Panels
  • PowerWizard 1.1 Control Panel (PWT1.1)
  • PowerWizard 2.1 Control Panel (PWT2.1)

Starting/Charging
  • Static battery charger
  • Battery

General
  • Remote fuel system connection
  • Electronic governor
  • Single point lift
  • Coolant heater
  • Combined stoneguard and transition flange
  • Low fuel level shutdown
  • Low fuel level alarm
  • High fuel level alarm
  • Low coolant temperature alarm
  • Low coolant level shutdown